Tercel Zeus
ESE AIR TERMINAL • MODEL RANGE

Tercel Zeus Lightning Protection Models

A dedicated product page containing only the Tercel Zeus ESE Air Terminal models and technical data shown in the supplied Tercel catalogue.

TZ-20TZ-40TZ-50TZ-63TZ-90NFC 17-102 (1995)

Tercel Zeus ESE Air Terminal

The supplied catalogue describes the Tercel Zeus system as a controlled-streamer ESE lightning conductor using ambient electric-field sensing and internal triggering electronics. This page intentionally contains no other lightning-arrester brand or unrelated product.

Tercel Zeus TZ-20 ESE Air Terminal
TERCEL ZEUS ESE AIR TERMINAL

TZ-20

Triggering time ΔT20 μs
ΔL20 m
Dimension40 cm
Weight3.5 kg

Tercel Zeus TZ-20 is an Early Streamer Emission air terminal from the Tercel Zeus range. According to the supplied catalogue, the range uses a stainless-steel enclosure and is specified to NFC 17-102 (1995).

Current capacity>200 kA (10/350 μs)Wind speed capacity>40 m/sMaterialStainless Steel
Tercel Zeus TZ-40 ESE Air Terminal
TERCEL ZEUS ESE AIR TERMINAL

TZ-40

Triggering time ΔT40 μs
ΔL40 m
Dimension39 cm
Weight3.8 kg

Tercel Zeus TZ-40 is an Early Streamer Emission air terminal from the Tercel Zeus range. According to the supplied catalogue, the range uses a stainless-steel enclosure and is specified to NFC 17-102 (1995).

Current capacity>200 kA (10/350 μs)Wind speed capacity>40 m/sMaterialStainless Steel
Tercel Zeus TZ-50 ESE Air Terminal
TERCEL ZEUS ESE AIR TERMINAL

TZ-50

Triggering time ΔT50 μs
ΔL50 m
Dimension37 cm
Weight3.5 kg

Tercel Zeus TZ-50 is an Early Streamer Emission air terminal from the Tercel Zeus range. According to the supplied catalogue, the range uses a stainless-steel enclosure and is specified to NFC 17-102 (1995).

Current capacity>200 kA (10/350 μs)Wind speed capacity>40 m/sMaterialStainless Steel
Tercel Zeus TZ-63 ESE Air Terminal
TERCEL ZEUS ESE AIR TERMINAL

TZ-63

Triggering time ΔT63 μs
ΔL63 m
Dimension39 cm
Weight4.0 kg

Tercel Zeus TZ-63 is an Early Streamer Emission air terminal from the Tercel Zeus range. According to the supplied catalogue, the range uses a stainless-steel enclosure and is specified to NFC 17-102 (1995).

Current capacity>200 kA (10/350 μs)Wind speed capacity>40 m/sMaterialStainless Steel
Tercel Zeus TZ-90 ESE Air Terminal
TERCEL ZEUS ESE AIR TERMINAL

TZ-90

Triggering time ΔT90 μs
ΔL90 m
Dimension40 cm
Weight4.5 kg

Tercel Zeus TZ-90 is an Early Streamer Emission air terminal from the Tercel Zeus range. According to the supplied catalogue, the range uses a stainless-steel enclosure and is specified to NFC 17-102 (1995).

Current capacity>200 kA (10/350 μs)Wind speed capacity>40 m/sMaterialStainless Steel

Protection Radius Tables

Protection radius values reproduced from the supplied Tercel catalogue. Heights and radii are in metres.

Level I — High Protection (D = 20 m)

Model / Height234678101520
TZ-20152229373838394040
TZ-40233546585959606060
TZ-50274155696969697070
TZ-63314763828282828383
TZ-90375875109109109110110110

Level II — Medium Protection (D = 45 m)

Model / Height2346810152045
TZ-20213041525353555860
TZ-40304560767677778081
TZ-50345269878787889092
TZ-63395878101101101102104105
TZ-904670101129130130130132133

Level III — Standard Protection (D = 60 m)

Model / Height23468102045
TZ-202335465961626669
TZ-403350678485878992
TZ-50385776969798100102
TZ-63436485111112114116
TZ-905084119141141143145
Where the supplied parsed catalogue does not clearly provide a value, the table shows “—” rather than adding an unsupported figure.